Taco PC705-2 Variable Speed Pump Control

Availability:
In-Stock
With the Taco Variable Speed Pump Mixing Control you can regulate the supply water temperature to a heating system by simultaneously controlling a boiler and the speed of an injection pump.

Based on the outdoor air temperature, the PC705 continuously adjusts the boiler differential to optimize the firing cycles of the boiler, prevent large water temperature swings and increase the efficiency of your system.

As the heating load changes, the Taco Mixing Control automatically adjusts the injector circulator, increasing its speed as load increases and slowing it with a decreasing load.

The Taco Mixing Control features full diagnostics, including a lighted bar graph that simulates the speed of the variable speed injection pump, warm weather shut down, a maximum supply water temperature setting, and a sensor that can be connected to the boiler to prevent corrosion in the unit due to flue gas condensation.

$711.00 USD

Title
Buy Now
SKU:
PC705-2
ID:
TC200-2S9-0439

SPECIFICATIONS


Application
Boiler Reset

Height
4-3/4"

Variable Pump
120 V (ac) 1.8 A 1/2 hp, fuse 2.5 A 250 V

Mix Design Temp
70 to 220°F

Outdoor Design Temp
-60 to 32°F

Warm Weather Shutoff Temp
Off, 35 F to 100 F

Power Method
24V

Ambient Conditions
Indoor use Only: 32°-104°F < 90% RH non-condensing



Width
2-7/8"

Depth (Inches)
1-7/8"

Sensor Type
1 outdoor air and 2 supply water

Mix Start
35 to 150°F

Boiler Min. Control Temp
Off, 80 to 180°F

Amperage
5

Voltage
24v

Relays
120 V (ac) 5 A - 1/3 hp pilot duty 240