ICM ICM533 3-Phase Surge Protective Device
Replaces: ABB: OVRHLDxx-120; ASCO: 420120Y, 420240D; Eaton: SP1-208Y, SP1-240D, SP2-208Y, SP2-240D; ERICO (Critec): TDX50C120/208, TDX50C120/240D; Intermatic: AG2083C3, L5F13Y1DG1; Leviton: 55208-ASA; Siemens: TPS3D, TPS3C; Square D: SDSA2040, SDSA2040D
$179.29 USD
PRODUCT INFO
The ICM530 Series is 4 models of Type 1 and Type 2, 3-phase Surge Protective Devices for 3-phase Delta and 3-phase Wye configurations.
When a surge occurs, the ICM three-phase surge suppressor will absorb the surge up to the specified limitations of the device. ICM incorporates superior thermally protected metal oxide varistor technology into the three-phase surge suppressors, which allows for safe disabling of the surge elements when a surge exceeds the thermal limits of the device. There is a single status light on the controls which identifies operational status when illuminated.
The ICM 3-phase surge suppressors can be installed as a Type 1 or Type 2 device for both indoor and outdoor applications.
SPECIFICATIONS
General Information | |
Service Voltage (3-Phase) | 120/240 VAC Delta High-Le |
Short Circuit Current Rating (SCCR) | 200 kA |
Nominal Discharge Current (In) | 20kA |
Maximum Surge Current | 150,000 amps |
Protection Mode | 3 for Delta configuration |
Maximum Continuous Operation Voltage (MCOV) | L-L: 300 VAC H-L: 450 VAC L-N: 150 VAC H-N: 300 VAC |
VPR | L-L: 1200 VAC H-L: 1500 VAC L-N: 700 VAC H-N: 900 VAC |
SPD Type | Type 1 (can also be used in Type 2 applications) |
Surge Protection Technology | TFMOV |
Input Power Frequency | 50/60 Hz |
WEIGHT/DIMENSIONS | 4.30” x 4.10” x 2.30” |