WebSwitch/ Remote Power Switch & Auto Reboot Device

Availability:
Out-Stock
Remote power switch | IP remote reboot & power control when reliability really matters.

$10,000.00 USD

Sold Out

SKU:
XRDI-WS3-NA; XRDI-WS3-IN

PRODUCT INFO

Overview | IP Controlled Power Strip
WebSwitch™ Remote Power Switch, is the ideal IP controlled power strip for remote power control, remote reboot, and automatic reboot of network devices using a standard web-browser.

        1. Two, Independent IP Controlled Power Outlets
WebSwitch has two power outlets which can be independently controlled over an IP network using a web browser on a computer or smartphone. It is completely self-contained and includes a built-in web server, so no external servers, or monthly subscriptions are required.


       2. Remote Power Control

Use WebSwitch as a remote control outlet that provides remote power control and/or automatic reboot of these devices: Servers, computers, routers, and other electrical devices.

       3. Automatic Reboot & Remote Reboot Device
When configured for automatic reboot, WebSwitch will periodically ping a designated IP address and wait for a response. If there is no response to the ping, WebSwitch will automatically reboot the powered device in an attempt to restore its normal operation.
If automatic reboot isn't configured, manual remote reboot can easily be achieved by a simple press of a button on the device's Control Page.

WebSwitch is available in two models, WebSwitch & WebSwitch Plus!
Both models are engineered to provide excellent performance for many years while running 24/7. You can be confident in using WebSwitch when your critical applications demand reliability and integrity.

Features:

WebSwitch

  • Independently control two power outlets using a standard web browser...no special software required.
  • Automatic reboot - Use to remotely reboot devices when ping responses fail.
  • Manual remote reboot
  • Built-in web server provides direct access to device...no external servers, services or subscriptions required.
  • Supports HTTP, SNMP, and Modbus/TCP.
  • "Remote Services" can be used to initiate connection with external servers.
  • Password protection.
  • IP filter provides simple firewall.
  • Selectable TCP Ports.
  • 10/100 Mbps Ethernet connectivity.
  • Field re-programmable; install firmware updates when available.
  • Attractive, rugged enclosure made of flame resistant plastic.
  • Operates worldwide (100-240V AC; 50/60Hz).
  • Wall mountable or optional rack mounting kit available.

WebSwitch Part Numbers:

       1. XRDI-WS3-NA   
OUTPUTS: 2 Relays (10A 100-240V AC (47-63Hz))
INPUTS: N/A
POWER SUPPLY: 100-240V AC (47-63Hz)

       2. XRDI-WS3-IN   
OUTPUTS: 2 Relays (10A 100-240V AC (47-63Hz))
INPUTS: N/A
POWER SUPPLY: 100-240V AC (47-63Hz)

Electromagnetic Compliance:

  • IEC CISPR 22, CISPR 24
  • FCC 47CFR15
  • EU EN55024, EN55022
  • EN55022:2006: Class B
  • EN61000-3-2
  • EN61000-3-3
  • EN55024:2006
  • IEC 61000-4-2
  • IEC 61000-4-3
  • IEC 61000-4-4
  • IEC 61000-4-5
  • IEC 61000-4-6
  • IEC 61000-4-8
  • IEC 61000-4-11
  • ITE-Class B

Product Safety Compliance:

  • CAN/CSA-C22.2 No.60950-1-03 First Edition
  • UL 60950-1 First Edition

Real-Time Clock:

  • Manual or NTP(Network Time Protocol) setup
  • NTP Sync Period: Once, Daily, Weekly, On Powerup
  • Auto Daylight Savings Adjustment
  • Battery (capacitor) Power Backup


SPECIFICATIONS

Relay Contacts

Number of Relays
2
Relay Connector
IEC C13 Female
Contact Type
SPDT (Form C)
Load Type
General Purpose
Contact Resistance
< 30 milliohms initial
Contact Material
AgSnO2
Electrical Life
100K cycles (Typical)
Mechanical Life
10M cycles (Typical)
Environmental Rating
Over voltage Category II, Pollution Degree 2
Relay Modes
ON/OFF or Pulse
Pulse Timer Duration
0.1 to 86,400 Seconds (1-day)

 

Network

Type10/100 Base-T Ethernet Port
LED Indicators

Number of LEDs

5 (Power on; Out On 1-2; Network linked; Network activity)


Password Settings
Password protection on setup page
Yes
Password protection on control page
Optional
Password Encoding
Base 64
Password Length10 Characters
ProtocolsHTTP, XML, Modbus TCP/IP, SNMP, Remote Services
Power Requirements
Voltage100-240V AC (47-63Hz)
Input Frequency
47-63Hz
Input Connector
IEC 320 Appliance Connector (C14 Male)
Max Current 10A (DO NOT USE WEBSWITCH TO CONTROL MORE THAN 10 AMPS - BOTH OUTLETS)

 

Physical
Size

10.65 inches (27.11 cm) wide
1.75 inches (4.44 cm) tall
3.29 inches (8.36 cm) deep

Operating Temperature
-4°F to 104°F (-20°C to 40°C)
Weight1.3 lb
Enclosure MaterialLexan 940 Polycarbonate Plastic
Enclosure Flame RatingUL94 V0

 

Logging
Log File Size512K (Max 17272 logs)
StorageNonvolatile Flash
Buffer ArchitectureCircular Buffer