R407A (R-32/R-125/R134a) (20/40/40 wt%)
PLEASE NOTE:
You EPA Certification or resale license to purchase this refrigerant
If you do not have certification, you must sign a statement with your full legal name stating you indent to resell the refrigerant to a certified person.
This ships via Hazmat signature is required for delivery.
$750.00 USD
PRODUCT INFO
- All components in our products are pure and Lab-Certified
- Cylinder comply with DOT-39
- 1/4" SAE Valve Connection
R-407A is a blend of R-32, R-125 and R-134A with similar properties to R-22. It is commonly used for medium and low temperature refrigeration applications and offers excellent capacity and efficiency as a replacement for R-404A and R-507 in new and existing R-404A equipment. New systems built with R407A must have POE lubricants and retrofitted R-22 systems need the residual oil changed to POE. It is non toxic and non flammable meeting the highest A1 Classification.
SPECIFICATIONS
Physical Properties | R407A | |
Classification | HFC | |
Molecular Weight | 90.1 | |
Boiling Point (1 atm, °F) | -49.9 | |
Critical Pressure (psia) | 658.6 | |
Critical Temperature (°F) | 181 | |
Critical Density, (lb./ft^ 3) | 31.4 | |
Liquid Density (70 °F, lb/ft^3) | 72.6 | |
Heat of Vaporization (bp, BTU/lb.) | 100.8 | |
Specific Heat Liquid (70 °F, BTU/lb.°F) | 0.3554 | |
Specific Heat Vapor (1 atm, 70 °F, BTU/lb. °F) | 0.1967 | |
Ozone Depletion Potential (CFC 11=1.0) | 0 | |
Global Warming Potential (CO2=1.0) | 2110 | |
ASHRAE Standard 34 Safety Rating | A1 | |
Temperature Glide (°F) | 8 |