Currencies
My Cart

Tecumseh ARGUS ASHR2460ZNAFS1 1-1/2 HP low temp condensing unit (outdoor rated)

Availability:
In-Stock

PRODUCT FAMILY : Argus
APPLICATION : LBP
VOLTAGE : 208-230V 1PH 60Hz
UNIT TYPE : Outdoor
REFRIGERANT : R-404A, R-448A, R-449A, R-452A
BRAND VERSION : ARGUS - Small
COIL TYPE : Tube - Fin
COMPRESSOR TECHNOLOGY : Reciprocating
FEATURE : Silver

Best-fit commercial refrigeration checks

Tecumseh ARGUS ASHR2460ZNAFS1 1-1/2 HP low temp condensing unit (outdoor rated) sits in the condenser and condensing unit side of a commercial refrigeration project. Buyers usually compare this category by medium-temp or low-temp application, BTU capacity, compressor type, refrigerant, voltage, phase, ambient conditions and matched evaporator or unit cooler.

  • Good fit: the temperature class, voltage, phase and refrigerant match the refrigeration schedule.
  • Great fit: capacity and compressor configuration are checked against the evaporator coil, unit cooler and box load.
  • Perfect-fit check: verify the condensing unit with the selected evaporator, controls, line-set plan and installation requirements before ordering.

For the full project path, compare walk-in cooler and freezer boxes, evaporator coils and unit coolers, and commercial refrigeration condensing units.

Call 760-478-7759 or CONTACT US for pricing and to place an order.
Title
SKU:
ASHR2460ZNAFS1
ID:
T100-0003

SPECIFICATIONS


StatusActive

Cooling TypeAir Cooled Unit

Relay TypePotential Relay

Length    722 MM(28.4IN)

Height471 MM(18.5IN)

Width717 MM(28.2IN)

Weight159LB(72KG)

Discharge Line Size3/8 in (9.52mm)

Suction Line Size5/8 in (15.9mm)

Compressor ModelAWA2450ZXD

LRA Start    56

Air Flow700 CFM

Design Pressure High450

Design Pressure Low181

Fan Motor RLA0.45

Minimum Circuit Ampacity12.4

Maximum Fuse Size20



Maximum Ambient Temperature110

Maximum Evaporation Temperature10

Minimum Ambient Temperature90

Minimum Evaporation Temperature    -40

Pump Down Capacity9.5 Lb

CondenserY

ContactorY

Crankcase HeaterY

Fan MotorY

Fan Motor Qty    1

High Pressure SwitchY

Low Pressure SwitchY

Pressure Control LowY

Primary RelayY

ReceiverY

Run CapacitorY

Start CapacitorY